  • Der Differenzdruckwächter von TiTEC Messtechnik
  • Differenzdruckwächter in der Zeichnung von TiTEC Messtechnik

DIFFERENTIAL PRESSURE CONTROLLER – DDW
DDW

TiTEC GmbH DDW

Anwendung

For monitoring incombustible and non-aggressive gaseous media. Our Differential Pressure Controllers are available with various measuring ranges and are delivered as standard with a connection set. Further features:
– Adjustable with large scale
– Metric cable glands
– Duct connection nipples: length 60 mm
– Horizontal or vertical mounting position

Technische Spezifikationen

 
Pressure ranges:see table
Pressure medium:Air, incombustible and nonaggressive gases
Protection class:IP54
Material housing:Switch casing PA 6.6, fastening parts POM
Life span:106 106 switching operations
Material diaphragm:Silicon
Temperature range:-20°C...+85°C
Max. operating excess pressure:50 mbar
Pressure connections:Plastic with a diameter of 6.00 mm
Switching capacity:1,0 A, 250 VAC
Electrical connection:Blade terminal 6.3x0.8mm pursuant to DIN 64244 with screw clamps up to 2.5 mm²
Accessories:Mounting kit:
2 plastic duct connection nipples
with mounting screws and 2m PVC hose Ø 6 mm
Data-Sheet

Merkmale

TypePressure RangesDifferential gapTolerance
DDW/H-1020...300 Pa10 Pa+/- 15%
DDW/H-2030...400 Pa15 Pa+/- 15%
DDW/H-4050...500 Pa20 Pa+/- 15%
DDW/H-50200...1000 Pa100 Pa+/- 15%