zurück zur Artikelliste
  • Der neue Drucktransmitter aus dem Hause TiTEC
  • Zeichnung Drucktransmitter von TiTEC_Messtechnik
  • Drucktransmitter in der Zeichnung von TiTEC_Messtechnik

Pressure Transmitter – DT1
DT1

TiTEC GmbH DT1

Anwendung

The pressure transmitters with ceramic measuring cell DT1 is ideal for measuring relative pressure of non-aggressive media. Applications can be found in building automation, industry, as well as pneumatic and hydraulic applications.

Technische Spezifikationen

 
General
Sensor relative
Measuring range see table
Bursting pressurex 2,5 FS (Fullscale)
Linearity< 1% FS
Hysteresis< 0,5 % FS
Temperature error / Offset0,03% FS/K
Temperature error / Measuring range0,05% FS/K
Operating temperature0 … 85°C
Protection classIP 65
ConnectionValve connector acc. DIN EN 175301-803-A M12-connector
Connection ThreadG1/2“ or G1/4“
Material Housing 1.4305Sensor AI2O3Seal Viton®
Typ I
Output4…20 mA
Connection2-wire
Nominal voltage24 VDC
Power supply12…30 VDC
Burden Ra[Ω]=(Uv[V]-10V) 0,02 A
Typ U
Output0…10 V
Connection3-wire
Nominal voltage24 V AC/DC
Power supply12…30 V AC/DC
Data-Sheet

Merkmale

 
Typ OutputPressure rangeConnection thread
DT 1 I = 4 … 20 mA01 = 0 … 1,6 bar01 = G1/4“
U = 0 … 10 V02 = 0 … 2,5 bar02 = G1/2“
00 = Sonder*/Special*03 = 0 … 4 bar00 = Sonder*
04 = 0 … 6 bar
05 = 0 … 10 bar
06 = 0 … 16 bar
07 = 0 … 25 bar
08 = 0 … 40 bar
09 = 0 … 60 bar
10 = -1 … 0 bar
11 = -1 … 0,6 bar
12 = -1 … 1,5 bar
13 = -1 … 3 bar
14 = -1 … 5 bar
15 = -1 … 9 bar
16 = -1 … 15 bar
17 = -0 … -1 bar
00 = Sonder*/Special*

Newsletter Login