zurück zur Artikelliste
  • Deckeneinbautemperaturfühler DEBF _ MU von TiTEC Messtechnik
  • Deckeneinbautemperaturfühler in der Zeichnung von TiTEC Messtechnik

CEILING-MOUNTED TEMPERATURE SENSOR – DEBF / MU
DEBF / MU

TiTEC GmbH DEBF / MU

Anwendung

For indoor temperature measuring applications (to be flush-mounted).The sensor features a plain and modern design and is mounted to the ceiling with the help of two tension springs. The DEBF is equipped with a standardized 0…10 V or 4…20mA output and can be connected to any PLC or DDC.

Technische Spezifikationen

 
Transmitter
Required temperature sensor:Pt1000 class B (2-wire)
Power supply:15-36 V/DC with 4-20 mA
15-36 V/DC, 24 V/AC with 0-10 V
Apparent ohmic resistance: 300-1000 Ohm (with 4-20 mA)
Load at analogue output:min. Load resistance 10 kOhm at 0-10 V
Power input with 0...10 V:20 mA
Power input with 4...20 mA:24-44mA
Accuracy:+/- 0,2K + max. 3% of final value
Measuring range:24 measuring ranges available
Operating temperature transmitter:-30°C ... +70°C
Connection:3-wire (2-wire optional with 4-20 mA)
Norms:CE, EMC pursuant to EN61326-1 2006, EMC directive 89/336/EEC
Temperature Sensor
Measuring range:See table
Temperature sensor:Pt1000 class B (2-wire)
Connection:Screw clamps, max 1.5 mm²
Material sensor:ceramics
Tmax. Housing:+100°C
Casing:PA6 15% GK, Colour RAL 9010
Housing dimensions:65 x 60 x 38 mm
Protection class:IP20
Data-Sheet

Merkmale

Item No.Output
DEBF/MUV0...10 V
DEBF/MUA4...20mA

Newsletter Anmeldung


Bitte senden Sie mir entsprechend Ihrer Datenschutzerklärung regelmäßig und jederzeit widerruflich Informationen zu folgendem Produktsortiment per E-Mail zu: Messtechnik und Sensorik