zurück zur Artikelliste
  • Der Tauchtemperaturfühler von TiTEC Messtechnik
  • Kanaltauchtemperaturfühler in der Zeichnung von TiTEC Messtechnik

DUCT/IMMERSION TEMPERATURE SENSOR
KNTF / MU

TiTEC GmbH KNTF / MU

Anwendung

Our Duct/Immersion temperature sensors are equipped with dew point resistance by default. In combination with an immersion sleeve, the KNTF can also be used for measuring the temperature of liquid/non-aggressive media. Gaseous media may be measured with help of our monuting flange MF. The sensors are equipped with a standardized 0…10 V or 4…20mA output and can be connected to any PLC or DDC.

Technische Spezifikationen

 
Transmitter
Required temperature sensor:Pt1000 class B (2-wire)
Power supply:15-36 V/DC with 4-20 mA
15-36 V/DC, 24 V/AC with 0-10 V
Apparent ohmic resistance:300-1000 Ohm (with 4-20 mA)
Load at analogue output:min. Load resistance 10 kOhm at 0-10 V
Power input with 0...10 V:20 mA
Power input with 4...20 mA:24-44 mA
Accuracy:±0,2K + max. 3 % of final value
Measuring range:24 measuring ranges available
Operating temperature transmitter:-30 °C … +70 °C
Connection:3-wire (2-wire optional with 4-20 mA)
Norms:CE, EMC pursuant to EN61326-1 2006,
EMC directive 89/336/EEC
Temperature Sensor
Measuring range (head):-50°C...+180°C - depending on sensor
Temperature sensor:Pt1000 class B (2-wire)
Connection:Screw clamps, max 1.5 mm²
Protective fitting:Ø 6 mm, VA
Tmax. (housing):+100 °C
Casing:PA6 15% GK, Colour RAL 9010
Housing dimensions:65 x 60 x 38 mm
Protection class:IP65
Mounting accessories (optional):Immersion sleeve, mounting flange