zurück zur Artikelliste
DUCT HYGROSTAT WITH INTERNAL AND EXTERNAL CONTROLS – KHY
DUCT HYGROSTAT WITH INTERNAL AND EXTERNAL CONTROLS – KHY
KHY
Anwendung
The HG80 Hygrostat is a two-level controller for controlling the relative humidity in air ducts of air-conditioning system, conditioning cabinets. The device is also applied in food storages, cooling chambers for fruits and vegatables, greenhouses of gardening companies, textile industry, paper and printing industry, movie industry and hospitals – basically in all places where humidity monitoring and control is required.
Technische Spezifikationen
Range of scale: | 30…100% r.h. |
Accuracy: | ± 3,5% r.h. within measuring range > 50% r. h. ± 4% r. h. within measuring range < 50% r. h. |
Operating range: | 35…95% r. h. |
Medium: | Air (nonaggressiv), depressurized |
Differential gap: | ca. 4% r. h. for 50% r. h. |
Max. Voltage: | 250 VAC |
Switching capacity of changeover contact: | Ohmic load (cos phi=1) 15A AC 230 V Inductive load (co phi=0,7) 2A AC 230 V Voltage 0,25A DC 230 V |
Switching capacity, minimum load: | 100 mA, 125 VAC |
Weight: | 700g |
Protection class KHY-A: | IP54 |
Protection class KHY-A: | IP65 |
Protection class: | III |
Adm. air velocity: | 8m/sec |
Medium temperature: | |
Operating temperature: | 0…+60°C |
Storage temperature: | -30…+60°C |
Merkmale
Type | Setting |
KHY-A | External |
KHY-I | Internal |