zurück zur Artikelliste
  • Kondensationswächter von TiTEC Messtechnik
  • Kondensationswächter in der Zeichnung von TiTEC Messtechnik

CONDENSATION MONITOR – KDW2 AND KDW2/EXT
KDW2 KDW2/EXT

TiTEC GmbH KDW2 KDW2/EXT

Anwendung

Our KDW2 and KDW2EXT condensation monitors are typically mounted to cooling and cold water pipes, cooling ceilings or other cooled surfaces. Both models offer reliable detection of condensation and protect the objects against the former. The KDW2Ext has an external measuring point and can easily be mounted in confined spaces. Our KDWs can be used as monitors on cooling ceilings and pipes and the additional internal switching output is capable of activating heatings or other actuators.

Technische Spezifikationen

 
Sensorik
Swichting point:Adjustable between 80 and 100 %
Switching hysteresisca 5% r. h.
Operating range:0…100% r. h.
Operating temperature:-30°C…+70°C
Dew:Admissible
Condensation:Temporarily admissible
Measuring medium:Ambient air without atmospheric pollution
Response time:ca. 120 sec at switching point from 75 % to condensation
Cablle length at KDWext:2000mm silicon
Power supply
Operating voltage:16 … 24 VDC or 24 VAC
Operting current (at 24 VDC):max. 30 mA with energized relay
Relaymax. 15 mA with deenergized relay
Function control:green LED when in operation
LED :red when relay is energized
Output circuit
Switchting characteristics:Isolated relay with switching contact, closed at normal operation (condensate-free). Open at missing operating voltage or forming of condensation.
Contact voltage:max. 60 Vss
Switching current:Max. 1 A AC/DC
Display:LED grün (operating voltage applied)
LED rot (relay energized)
Switching capacity:60V/1A
Data-Sheet

Merkmale

TypeOutputDisplay
KDW2Relaisno
KDW2extRelaisno

Newsletter Anmeldung


Bitte senden Sie mir entsprechend Ihrer Datenschutzerklärung regelmäßig und jederzeit widerruflich Informationen zu folgendem Produktsortiment per E-Mail zu: Messtechnik und Sensorik