zurück zur Artikelliste
MEAN VALUE DUCT TEMPERATURE SENSOR
MEAN VALUE DUCT TEMPERATURE SENSOR
MWTF / MU
Anwendung
For measuring the temperature in gaseous media (when combined with a mounting flange). The fields of application are heating, ventilation and refrigeration engineering as well as air-conditioning. The sensors are equipped with a standardized 0…10 V or 4…20mA output and can be connected to any PLC or DDC.
Technische Spezifikationen
Transmitter | |
Required temperature sensor: | Pt1000 class B (2-wire) |
Power supply: | Bei 4 … 20 mA = 15 … 36 VDC |
Bei 0 … 10 V = 15 … 36 VDC, 24 VAC | |
Apparent ohmic resistance: | 300-1000 Ohm (with 4-20 mA) |
Load at analogue output: | min. Load resistance 10 kOhm at 0-10 V |
Power input with 0...10 V: | 20 mA |
Power input with 4...20 mA: | 24 … 44 mA |
Accuracy: | ±0,2K + max. 3 % of final value |
Measuring range: | 24 measuring ranges available |
Operating temperature transmitter: | -30 °C … + 70 °C |
Connection: | 3-wire (2-wire optional with 4-20 mA) |
Norms: | CE, EMV according to EN61326-1 2006, EMV Richtlinie 89/336/EWG |
Temperature Sensor | |
Measuring range (sensor capillary): | -30 °C … +80 °C |
Temperature sensor: | Pt1000 class B (2-wire) |
Connection: | Screw clamps, max 1.5 mm² |
Sensor capillary: | 4 x 0.5 mm copper, length: (see table) |
Tmax. (housing): | +100 °C |
Casing: | PA6 15% GK, Colour RAL 9010 |
Housing dimensions: | 65 x 60 x 38 mm |
Protection class: | IP65 |
Mounting accessories (optional): | mounting bracket, mounting flange |