  • Kanaltemperaturfühler von TiTEC Messtechnik
  • MWTF-Zeichnung Mittelwertkanaltemperaturfühler von TiTEC Messtechnik

MEAN VALUE DUCT TEMPERATURE SENSOR
MWTF / MU

TiTEC GmbH MWTF / MU

Anwendung

For measuring the temperature in gaseous media (when combined with a mounting flange). The fields of application are heating, ventilation and refrigeration engineering as well as air-conditioning. The sensors are equipped with a standardized 0…10 V or 4…20mA output and can be connected to any PLC or DDC.

Technische Spezifikationen

 
Transmitter
Required temperature sensor:Pt1000 class B (2-wire)
Power supply:Bei 4 … 20 mA = 15 … 36 VDC
Bei 0 … 10 V = 15 … 36 VDC, 24 VAC
Apparent ohmic resistance:300-1000 Ohm (with 4-20 mA)
Load at analogue output:min. Load resistance 10 kOhm at 0-10 V
Power input with 0...10 V:20 mA
Power input with 4...20 mA:24 … 44 mA
Accuracy:±0,2K + max. 3 % of final value
Measuring range:24 measuring ranges available
Operating temperature transmitter:-30 °C … + 70 °C
Connection:3-wire (2-wire optional with 4-20 mA)
Norms:CE, EMV according to EN61326-1 2006,
EMV Richtlinie 89/336/EWG
Temperature Sensor
Measuring range (sensor capillary):-30 °C … +80 °C
Temperature sensor:Pt1000 class B (2-wire)
Connection:Screw clamps, max 1.5 mm²
Sensor capillary:4 x 0.5 mm copper, length: (see table)
Tmax. (housing):+100 °C
Casing:PA6 15% GK, Colour RAL 9010
Housing dimensions:65 x 60 x 38 mm
Protection class:IP65
Mounting accessories (optional):mounting bracket, mounting flange