zurück zur Artikelliste

DIN RAIL TRANSMITTER FOR THERMOCOUPLES TYPE K – MUF-HS-TE
MUF-HS-TE

TiTEC GmbH MUF-HS-TE

Anwendung

Our measuring transducer MUF-HS-TE records the temperature via a connected thermocouple NiCr-Ni, Typ K and coverts the value into a standardized analogue output signal in the range between 0-10V/4-20 mA.

Measuring ranges can be selected and adjusted with the help of a DIP switch.
On request additional options can be offered.

Offset can be corrected by ±8°K using the potentiometer.

Technische Spezifikationen

 
Power supply U 12 … 24 V AC/DC
Power supply I 12 … 24 V DC
Analogue output burden: 250 … 600 Ohm (4 … 20 mA)
Analogue output load: 10 ... 100 kOhm (0 … 10 V)
Current consumption 0 … 10 V: 20 mA
Current consumption 4 … 20 mA: 24 … 44 mA
Connection 3-wire (4-20 mA optional 2-wire)
Tolerance temperature: Depends on used TC
Potentiometer: Offset ± 8°K
Measurement ranges: 9 measurement ranges selectable
Operating temperature MUF -40 °C … +85 °C
Needed temperature sensor Thermocouple NiCr-Ni, Type K
Connection Screw-In terminals 1,5 mm²
Casing material Polycarbonat PC-F
Dimension Casing (L x W x H) 15 x 75 x 53 mm
Flammability UL 94: V0
Protection classIP20
Standards DIN EN 61326-2-1:201, EG Directive 2004/108/EG